Kyoritsu Multi Function Tester model 6010A: works perfectly
Like new condition
Description
Kyoritsu 6010A Offers
Features
Continuity and Insulation Testing
Live circuit warning LED: Immediately notification if the circuit under test is live
Auto Discharge: Allows fast and safe discharge of electrical energy stored in capacitive circuits following testing
Integral overload protection on internal continuity and insulation test circuitry
Autoranging
500V DC test voltage for insulation tests
200 mA short circuit current on continuity ranges
Loop and RCD Testing
Wiring connection check LED's: Immediate indication if wiring of circuit under test is correct
Overheat Protection: Rapid detection of overheating of internal circuitry, display of warning signal to user and automatic halting of measurement
Supply Voltage Indication: Can display supply voltage value in loop impedance mode
Low Current Loop Impedance Test: Short duration low test current will prevent tripping of many passive RCDs
Auto Data Hold: Retains displayed reading for set period following test
Phase Angle Selection: Selection of test current from +ve or -ve half cycle of waveform can prevent tripping of polarized type RCDs
Kyoritsu 6010A Specifications
Continuity Testing
Measuring Ranges 20/200 Ω Autoranging
Open Circuit Voltage 4 V
Short Circuit Current 200 mA DC
Accuracy ±(3%rdg+3dgt)
Insulation Testing
Measuring Ranges 20/200 Ω Autoranging
Test Voltage 500V DC
Output Voltage on Open Circuit 570 V DC ±6%
Rated Current 1 mA
Accuracy ±(3%rdg+3dgt)
Loop Impedance Testing
Rated Voltage 230V AC ±10% @ 50 Hz
Voltage Measuring Range 100 to 250 V @ 50 Hz
Impedance Ranges 20/2000 Ω
Nominal Test Current 20 Ω Range: 24 A
2000 Ω Range: 15 mA
Accuracy 20 Ω Range: ±(3%rdg+8dgt)
2000 Ω Range: ±(3%rdg+8dgt)
RCD Testing
Rated Voltage 230V AC ±10% @ 50 Hz
Trip Current Settings RCD x 1/2: 5, 15, 50, 150, 250 mA
RCD x 1: 10, 30,100,300,500 mA
RCD Fast: 150 mA
Trip Current Duration RCD x 1/2 x 1: 2000 ms
RCD fast: 40 ms
Trip Current ±3% of test current at 230 V
Trip time ±(3%rdg+3dgt)
General Specifications
Safety Standard IEC 61010-1 CAT.Ⅲ 300V Pollution degree 2
Withstand Voltage 3700V AC for one minute
Note:
Pictures are of actual item and form part of the description.
Please check the photos to see the condition of the item for sale and what is included